UVC-Aire
Air Curtain

UV-C Light System For Air Purification Unheated Air Curtain

Unheated

The UVC-Aire offers a variable speed air curtain in a stainless-steel case. ¾ HP motors run continuously on low speed to provide a constant stream of purified air. Low-speed operation of the unit has been proven to inactivate/kill up to 99% of Coronavirus pathogens passing through the air curtain. The UVC-Aire is ideal for healthcare, retail, gyms, restaurants and other facilities looking to provide an added layer of protection against airborne germs.


Unit Sizing

Unit Widths:
from 3' to 12'
Motors:
3/4 HP
Mount Type:
Above Ceiling
Max Install Height:
14'
UVC Light Wavelength:
253.7nm
COVID-19 Kill Rate:
99.01 to 99.71% dependent on unit/speed
For Door Widths Between
36" and 168"

How the UVC-Aire Protects

  1. Germs, viruses and bacteria are pulled into the air curtain
  2. Upon entering, the harmful pathogens are exposed to and inactivated by UV-C light
  3. The discharged air is significantly reduced of dangerous pathogens such as the Coronavirus

UVC-Aire Retrofit Extension

Extension of the case for retrofit of previously installed air curtains.

  • UVC-Aire –Powered Aire’s air sanitation system proven to eliminate Covid-19 and other viruses from the air at up to a 99.9% effectiveness rate.
  • Designed to retrofit on most existing unheated or electrically heated commercial or low-profile units
  • Quick and easy installation – easily extend the case length with emitters and new filter.
  • Plug-and-Play with 120 Volt Power Supply. Emitters will continuously operate independent of air curtain operation.
  • Simply move existing intake screen and filters to be to the front of the extension.

Cost Savings Calculator

This tool will help you understand the cost savings you could expect based on the air curtain you select and your input on how and where it will be used.

Calculate Now

Air Curtain Selector

This tool is designed to help you find the best air curtain
for your situation by asking a few basic questions.

Begin
UVC-Aire Air Curtain | Performance Table
MODEL Nozzle Width (in.) Max FPM at Nozzle Average Outlet Velocity (FPM) Airflow Rate (CFM) Outlet Velocity Uniformity Power Rating (kW) Number of Motors Motor HP Weight (lbs) Coronavirus Inactivation Rate Number of Emitters
UVC-1-36 36 5654 2060 1401 88% 0.76 1 3/4 110 99.01 2
UVC-1-42 42 5321 2022 1678 88% 0.84 1 3/4 118 99.15 2
UVC-1-48 48 5296 1849 1757 84% 0.86 1 3/4 125 99.56 2
UVC-1-60 60 5288 1619 2007 72% 0.94 1 3/4 139 99.71 2
UVC-2-72 72 5654 2060 2802 88% 1.52 2 3/4 193 99.44 2
UVC-2-84 84 5321 2022 3356 88% 1.68 2 3/4 212 99.26 4
UVC-2-96 96 5296 1849 3514 84% 1.72 2 3/4 231 99.62 4
UVC-3-108 108 5654 2060 4203 88% 2.28 3 3/4 275 99.63 4
UVC-3-120 118 5340 2033 4757 88% 2.44 3 3/4 306 99.61 4
UVC-3-132 133 5305 1860 4809 72% 2.46 3 3/4 336 99.61 4
UVC-4-144 145 5654 2060 5604 88% 3.04 4 3/4 388 99.48 4
UVC-Aire Air Curtain | Mechanical Information Table
MODEL Overall Width (in.) Nozzle Width (in.) Mounting Width (in.)
UVC-1-36 36 37 36.06
UVC-1-42 42 43 42.06
UVC-1-48 48 49 48.06
UVC-1-60 60 61 60.06
UVC-2-72 72 73 72.06
UVC-2-84 84 85 84.06
UVC-2-96 96 97 96.06
UVC-3-108 108 109 108.06
UVC-3-120 118 119 118.06
UVC-3-132 133 134 133.06
UVC-4-144 145 146 145.06