THS-HW
Air Curtain

Climate Control (THS-HW) Hot Water Heated Air Curtain

Hot Water

The THS-HW air curtain provides a heated barrier of air that helps improve comfort and energy efficiency. This air curtain is ideal for climate control applications in retail, commerical and office settings. The highly efficient THS uses a plenum to provide consistent and equal coverage across the entire width of the door. It is ideal for hospitals, apartment buildings and other facilities relying on a hot water-based heat system.

When requesting a quote for a Hot Water-heated air curtain, please provide:
• Specifics of water/steam entering and exiting the air curtain.
• Location for water/steam supplies and returns (both on one side or one each side)


Unit Sizing

Unit Widths:
from 3' to 12'
Motors:
3/4 HP
Mount Type:
Exposed
Max Install Height:
12'
Wind Stoppage Ability:
= 17.3mph

Key Design Features

  • Outer cabinet constructed of 18-gauge 304 stainless steel with #3 finish
  • 3/4 HP ODP (Open Drip Proof) direct-drive dual-speed motor(s)
  • High-efficiency discharge plenum with adjustable air foil vane (+/-20˚)
  • Top and bottom access panels for servicing and removal of motor-blower assembly
  • NEMA 12 control panel
  • Coil made to AHRI Standard 410
  • Hot water coil comprised of galvanized steel casing, 5/8" copper tube, aluminum fins, and same end supply/return connections
  • Leak tested at 450 psi
  • Single length hot water coils up to 14 ft
  • Single length steam coils up to 10 ft
  • Custom coil selections available (consult factory)

Recommended Air Curtain Controls

  • Activation by 24V magnetic door switch
  • Toggle disconnect switch
  • Hand/Off/Auto selector switch
  • Heat On/Off selector switch
  • Digital thermostat
  • Hot water or steam control valve with actuator

360 View

360 View | THS-HW - Climate Control (THS-HW) Hot Water Heated Air Curtain

Cost Savings Calculator

This tool will help you understand the cost savings you could expect based on the air curtain you select and your input on how and where it will be used.

Calculate Now

Air Curtain Selector

This tool is designed to help you find the best air curtain
for your situation by asking a few basic questions.

Begin
THS-HW Air Curtain | Performance Table
Hot Water
MODEL Nozzle Widtd (in.) Max. FPM
at Nozzle
Avg. FPM Max. CFM CFM at Nozzle Outlet Velocity Uniformity Number of Motors Motor HP mbtu
/ Hour
Temp. Rise (˚F) Weight
(lbs)
THS-1-36HW 36 H: 4218
L: 2837
H: 3695
L: 2487
H: 2899
L: 1950
H: 2541
L: 1710
95% 1 3/4 97 H: 35
L: 52
113
THS-1-48HW 48 H: 4218
L: 2837
H: 2771
L: 1865
H: 3867
L: 2601
H: 2559
L: 1721
92% 1 3/4 102 H: 37
L: 54
145
THS-1-60HW 60 H: 4218
L: 2837
H: 2218
L: 1493
H: 4374
L: 2792
H: 2528
L: 1703
91% 1 3/4 100 H: 36
L: 54
180
THS-2-72HW 72 H: 4218
L: 2837
H: 3696
L: 2488
H: 5803
L: 3903
H: 5082
L: 3420
95% 2 3/4 194 H: 35
L: 52
249
THS-2-84HW 84 H: 4218
L: 2837
H: 3169
L: 2133
H: 6766
L: 4551
H: 5063
L: 3382
93% 2 3/4 205 H: 37
L: 55
281
THS-2-96HW 96 H: 4218
L: 2837
H: 2773
L: 1866
H: 7732
L: 5201
H: 5081
L: 3417
92% 2 3/4 194 H: 35
L: 52
306
THS-2-108HW 108 H: 4218
L: 2837
H: 2472
L: 1661
H: 8216
L: 5520
H: 5090
L: 3421
95% 2 3/4 192 H: 35
L: 52
329
THS-3-108HW 108 H: 4218
L: 2837
H: 3702
L: 2486
H: 8702
L: 5853
H: 7623
L: 5130
92% 3 3/4 283 H: 34
L: 51
365
THS-3-120HW 120 H: 4218
L: 2837
H: 3174
L: 2134
H: 9668
L: 6503
H: 7614
L: 5127
95% 3 3/4 307 H: 37
L: 55
406
THS-3-132HW 132 H: 4218
L: 2837
H: 2792
L: 1885
H: 10177
L: 7155
H: 7589
L: 5104
95% 3 3/4 307 H: 37
L: 55
470
THS-4-144HW 144 H: 4218
L: 2837
H: 3696
L: 2488
H: 11606
L: 7806
H: 10164
L: 6840
95% 4 3/4 388 H: 35
L: 52
491