EVE-E
Air Curtain

Elite Vestibule Exception (EVE) Electric Heated Climate Control Air Curtain

Electric

The Elite Vestibule Exception (EVE) merges aesthetics and performance into a fashionable, low-profile air curtain designed for front-entry applications. As its name implies, the EVE can be used as an exception to costly, space-consuming vestibules. The unit has met all criteria per various vestibule codes. It has also been tested in accordance with the ANSI/AMCA 220 standard. The electrically heated unit is ideal for locations with colder winter months.

A heated barrier prevents the infiltration of cold air when a door is open. The EVE-E has a stylish intake accompanied with rounded edges to create a curved, contemporary silhouette. Available in brushed stainless steel, white powder coat or black powder coat, the EVE blends into a building’s architectural design and layout.


Unit Sizing

Unit Width:
3'-10'
Motor:
1/5 HP
Mount Type:
Exposed
Max Install Height:
12'
Wind Stoppage Ability:
= 15.0mph

Key Design Features

  • Meets current ASHRAE 90.1 and IECC requirements for vestibule exception
  • 18-gauge 304 stainless steel in a number three finish (for brushed stainless steel units only)
  • The motor/blower plate comes out of the unit as an entire piece and the electrical connections can be made on the top or sides of the unit for more versatility
  • Available in brushed stainless steel, white powder coat and black powder coat

Air Curtain Controls

  • ON/OFF Switch
  • Variable Speed Switch with 120, 208 or 240 voltage
  • Built-in Time Delay Relay
  • Thermostat
  • Magnetic Door Switch for activation

360 View

360 View | EVE-E - Elite Vestibule Exception (EVE) Electric Heated Climate Control Air Curtain

Cost Savings Calculator

This tool will help you understand the cost savings you could expect based on the air curtain you select and your input on how and where it will be used.

Calculate Now

Air Curtain Selector

This tool is designed to help you find the best air curtain
for your situation by asking a few basic questions.

Begin
EVE-E Air Curtain | Performance Table
Electric Heat
MODEL Nozzle Width (in.) Max. FPM at Nozzle Avg. Outlet Velocity FPM Airflow Rate (CFM) Outlet Velocity Uniformity Power Rating (kW) Number of Motors Motor HP Heater kW Temp. Rise (˚F) Weight (lbs)
EVE-1-36E 35 3262 1316 961 87% 0.27 1 1/5 8 27 59
EVE-1-42E 41 3269 1294 1100 75% 0.29 1 1/5 8 23 69
EVE-1-48E 48 3256 1386 1344 85% 0.33 1 1/5 16 38 77
EVE-1-60E 59 3218 1406 1715 83% 0.54 1 1/5 16 30 91
EVE-2-72E 71 3262 1316 1922 87% 0.54 2 1/5 16 27 102
EVE-2-84E 83 3269 1294 2200 75% 0.58 2 1/5 24 35 115
EVE-2-96E 95 3256 1386 2688 85% 0.66 2 1/5 32 38 123
EVE-2-108E 107 3242 1397 3059 83% 0.87 2 1/5 32 33 139
EVE-2-120E 117 3218 1406 3430 83% 1.08 2 1/5 32 30 152
EVE-E Air Curtain | Mechanical Information Table
MODEL Overall Width (in.) Mounting Width (in.) Nozzle Width (in.)
EVE-1-36E 37 36 35
EVE-1-42E 43 42 41
EVE-1-48E 49 48 47
EVE-1-60E 61 60 59
EVE-2-72E 73 72 71
EVE-2-84E 85 84 83
EVE-2-96E 97 96 95
EVE-2-108E 109 108 107
EVE-2-120E 119 118 117