CED-E
Air Curtain

Customer Entrance Door (CED-E) Vestibule Exception Electrically Heated Air Curtain

Electric

The heated version of the Customer Entrance Door (CED) from Powered Aire adds a heating element to this popular air curtain. The unit is ideal for use in areas receiving large amounts of pedestrian traffic and is commonly found in high-traffic retail facilities where customer satisfaction is key.

The heated CED creates a thermal barrier that maximizes the comfort of those within the area. It also keeps conditioned air inside and unwanted elements out. The CED-E has a gentle airflow and its unique plenum design helps make it one of the quietest air curtains in the industry. The CED-E can be used as an exception to vestibules, having met all the necessary codes and has been tested in accordance with the ANSI/AMCA 220 standard.


Unit Sizing

Unit Widths:
from 3' to 14'
Motors:
1/2 HP
Mount Type:
Exposed
Max Install Height:
11'
Wind Stoppage Ability:
= 13.7mph

Key Design Features

  • Meets ASHRAE 90.1 and IECC requirements for vestibule exception
  • AMCA tested performance
  • Outer cabinet constructed of 18-gauge 304 stainless steel with #3 finish
  • 1/2 HP ODP (Open Drip Proof) direct-drive dual-speed motor(s)
  • High-efficiency discharge plenum with adjustable air foil vane (+/-20˚)
  • Factory mounted single-stage electric heaters
  • Single point power connection available (see electrical table)
  • Alternate heater kW available (consult factory)

Recommended Air Curtain Controls

  • Activation by 24V magnetic door switch
  • Toggle disconnect switch
  • SmartTouch controller
  • Filter (washable)

360 View

360 View | CED-E - Customer Entrance Door (CED-E) Vestibule Exception Electrically Heated Air Curtain

Cost Savings Calculator

This tool will help you understand the cost savings you could expect based on the air curtain you select and your input on how and where it will be used.

Calculate Now

Air Curtain Selector

This tool is designed to help you find the best air curtain
for your situation by asking a few basic questions.

Begin
CED-E Air Curtain | Performance Table
Electric Heat
MODEL Nozzle Width (in.) Max. FPM at Nozzle Avg. Outlet Velocity (FPM) Airflow Rate (CFM) Outlet Velocity Uniformity Power Rating (kW) Number of Motors Motor HP Heater kW Temp. Rise (˚F) Weight (lbs)
CED-1-36E 36 3000 1074 795 87% 0.24 1 1/2 10 40 88
CED-1-42E 42 3000 1030 886 96% 0.24 1 1/2 10 36 95
CED-1-48E 48 3000 987 967 94% 0.25 1 1/2 10 33 102
CED-1-60E 60 3000 822 1011 89% 0.25 1 1/2 10 32 113
CED-2-72E 72 3000 1074 1590 87% 0.48 2 1/2 20 40 172
CED-2-84E 84 3000 1030 1772 96% 0.48 2 1/2 20 36 192
CED-2-96E 96 3000 987 1934 94% 0.50 2 1/2 20 33 206
CED-3-108E 108 3000 1074 2385 87% 0.72 3 1/2 30 40 244
CED-3-120E 118 3000 1039 2557 87% 0.73 3 1/2 30 37 272
CED-3-132E 133 3000 9660 2601 87% 0.73 3 1/2 30 37 285
CED-4-144E 145 3000 1074 3180 87% 0.96 4 1/2 40 40 344
CED-4-156E 157 3000 1051 3362 87% 0.96 4 1/2 40 38 362
CED-4-168E 169 3000 1030 3554 96% 0.96 4 1/2 40 36 380
CED-E Air Curtain | Mechanical Information Table
MODEL Overall Width (in.) Nozzle Width (in.) Mounting Width (in.)
CED-1-36E 37 36 36.06
CED-1-42E 43 42 42.06
CED-1-48E 49 48 48.06
CED-1-60E 61 60 60.06
CED-2-72E 73 72 72.06
CED-2-84E 85 84 84.06
CED-2-96E 97 96 96.06
CED-3-108E 109 108 108.06
CED-3-120E 119 118 118.06
CED-3-132E 134 133 133.06
CED-4-144E 146 145 145.06
CED-4-156E 158 157 157.06
CED-4-168E 170 169 169.06