EVE-ST
Air Curtain

Elite Vestibule Exception (EVE-ST) Steam Heated Air Curtain

Steam

The EVE ST offers the architecturally pleasing aesthetics found in all Elite Vestibule Exception (EVE) units but is fitted for applications where Steam is the primary source for heating. The steam valves protrude from the unit’s side for easy connection to pre-existing pipes. The EVE ST has been tested in accordance with the ANSI/AMCA 220 standard and can be used as an exception to vestibules in commercial applications including grocery stores, retail stores, restaurants, offices, and other new construction applications where a vestibule can be eliminated and replaced by an air curtain.


Unit Sizing

Unit Width:
3'-10'
Motor:
1/5 HP
Mount Type:
Exposed
Max Install Height:
12'
Wind Stoppage Ability:
= 15.0mph

Key Design Features

  • Meets current ASHRAE 90.1 and IECC requirements for vestibule exception
  • Steam-based unit adapts to buildings using Steam as primary means of heating
  • 18-gauge 304 stainless steel in a number three finish (for brushed stainless steel units only)
  • The motor/blower plate comes out of the unit as an entire piece and the electrical connections can be made on the top or sides of the unit for more versatility
  • Available in brushed stainless steel, white powder coat and black powder coat
  • Architectural design blends into building's aesthetics
  • Steam or hot water coil mounted to intake of air curtain. Coil consists of 5/8 in. O.D. copper tubes and aluminum fins. Coils certified to ARI standard 410
  • Control Panel included

Air Curtain Controls

  • Magnetic door switch for activation
  • Built in time delay relay

360 View

360 View | EVE-ST - Elite Vestibule Exception (EVE-ST) Steam Heated Air Curtain

Cost Savings Calculator

This tool will help you understand the cost savings you could expect based on the air curtain you select and your input on how and where it will be used.

Calculate Now

Air Curtain Selector

This tool is designed to help you find the best air curtain
for your situation by asking a few basic questions.

Begin
EVE-ST Air Curtain | Performance Table
Steam
Model Overall Width (in.) Nozzle Width (in.) Max. FPM at Nozzle Avg. Outlet Velocity (FPM) Airflow Rate (CFM) Outlet Velocity Uniformity Number of Motors Motor HP mbtu/Hour Temp. Rise (˚F) Weight
EVE-1-36ST 36" 35 3262 1348 984 84% 1 1/5 53 39 36
EVE-1-42ST 42" 41 3269 1462 1243 84% 1 1/5 60 47 35
EVE-1-48ST 48" 48 3256 1520 1474 85% 1 1/5 67 55 35
EVE-1-60ST 60" 59 3218 1529 1865 84% 1 1/5 85 70 35
EVE-2-72ST 72" 71 3262 1348 1968 84% 2 1/5 94 72 34
EVE-2-84ST 84" 83 3269 1462 2486 84% 2 1/5 105 97 36
EVE-2-96ST 96" 95 3256 1520 2948 85% 2 1/5 114 113 36
EVE-2-108ST 108" 107 3242 1525 3339 84% 2 1/5 130 128 35
EVE-2-120ST 120" 117 3218 1529 3730 84% 2 1/5 141 142 35

For other coil capacities consult factory. Heater data based on AMCA licensed values from unheated units