CED-HW
Air Curtain

Customer Entrance Door (CED-HW) Hot Water Heated Air Curtain

Hot Water

The CED-HW has been upgraded into a low-profile commercial case designed to a higher degree of aesthetics. All how water coils are contained within the case, providing a cleaner look while ensuring the highest level of performance. The CED HW is ideal for high traffic retail facilities and uses hot water coils to block cold outside air from entering through the heated barrier of air. Of additional benefit, the CED HW provides supplemental heat to areas around the door that are traditionally prone to an influx of cold air.


Unit Sizing

Unit Widths:
from 3' to 12'
Motors:
1/2 HP
Mount Type:
Exposed
Max Install Height:
11'
Wind Stoppage Ability:
= 13.7mph

Key Design Features

  • Outer cabinet constructed of 18-gauge 304 stainless steel with #3 finish
  • 1/2 HP ODP (Open Drip Proof) direct-drive dual-speed motor(s)
  • High-efficiency discharge plenum with adjustable air foil vane (+/-20˚)
  • Top and bottom access panels for servicing and removal of motor-blower assembly
  • NEMA 12 control panel
  • Coil made to AHRI Standard 410
  • Hot water coil comprised of galvanized steel casing, 5/8" copper tube, aluminum fins, and same end supply/return connections
  • Leak tested at 450 psi
  • Single length steam coils up to 10 ft
  • Custom coil selections available (consult factory)

Recommended Air Curtain Controls

  • Activation by 24V magnetic door switch
  • Toggle disconnect switch
  • SmartTouch controller
  • Hot water or steam control valve with actuator

360 View

360 View | CED-HW - Customer Entrance Door (CED-HW) Hot Water Heated Air Curtain

Cost Savings Calculator

This tool will help you understand the cost savings you could expect based on the air curtain you select and your input on how and where it will be used.

Calculate Now

Air Curtain Selector

This tool is designed to help you find the best air curtain
for your situation by asking a few basic questions.

Begin
CED-HW Air Curtain | Performance Table
Hot Water
MODEL Nozzle Width (in.) Max. FPM at Nozzle Avg. FPM CFM at Nozzle Outlet Velocity Uniformity Number of Motors Motor HP mbtu / Hour Temp. Rise (˚F) Weight (lbs)
CED-1-36HW 36 3000 1205 892 88% 1 1/2 34.6 35.8 104
CED-1-42HW 42 3000 1209 1040 90% 1 1/2 40.0 35.4 114
CED-1-48HW 48 3000 1131 1108 89% 1 1/2 41.8 34.7 124
CED-1-60HW 60 3000 998 1227 79% 1 1/2 47.7 35.8 143
CED-2-72HW 72 3000 1205 1784 88% 2 1/2 70.5 36.4 200
CED-2-84HW 84 3000 1209 2080 90% 2 1/2 78.5 34.8 226
CED-2-96HW 96 3000 1131 2216 89% 2 1/2 87.0 36.2 246
CED-3-108HW 108 3000 1205 2676 88% 3 1/2 103.1 35.5 295
CED-3-120HW 120 3000 1176 2892 88% 3 1/2 112.4 35.8 328
CED-3-132HW 132 3000 1111 3011 79% 3 1/2 113.9 34.9 344
CED-4-144HW 144 3000 1205 3568 88% 4 1/2 99.6 35.7 399
CED-4-156HW 156 3000 1208 3864 88% 4 1/2 142.8 34.0 422
CED-4-168HW 168 3000 1209 4160 90% 4 1/2 154.2 34.2 446
CED-HW/ST | Mechanical Information Table
MODEL Overall Width (in.) Nozzle Width (in.) Mounting Width (in.)
CED-1-36HW/ST 37 36 36.06
CED-1-42HW/ST 43 42 42.06
CED-1-48HW/ST 49 48 48.06
CED-1-60HW/ST 61 60 60.06
CED-2-72HW/ST 73 72 72.06
CED-2-84HW/ST 85 84 84.06
CED-2-96HW/ST 97 96 96.06
CED-3-108HW/ST 109 108 108.06
CED-3-120HW/ST 119 118 118.06
CED-3-132HW/ST 134 133 133.06
CED-4-144HW/ST 146 145 145.06
CED-4-156HW/ST 158 157 157.06
CED-4-168HW/ST 170 169 169.06